4-72 centrifugal fan
Source: Release time: 2017-07-07 Click: 657 times


  • I. Features and uses
    The 4-72 type centrifugal fan can be used for indoor ventilation and ventilation of general factories and large buildings, and transports air and other non-self-igniting, harmless to human body, and non-corrosive steel materials. B4-72 type ventilator can be used for ventilation of flammable volatile gas. Viscous substances are not allowed in the gas, and the dust and hard particles are not more than 150mg / m 3 . The gas temperature must not exceed 80 o C.
    The performance and options of the B4-72 fan and the size of the foundation are consistent with the 4-72 type, which can be selected according to its sample. The structure of the fan is basically the same as that of the 4-72 type. No2.8 ~ 6A adopts B35 type motor with flange and foot. No6 ~ 12C and D motors use the YB series corresponding to the Y series in this table. The installation type is B3 .
    Performance parameter table of 4-72 and B4-72 centrifugal fans
    The parameters provided in the performance table are calculated according to the standard inlet state of the fan unless otherwise specified, that is, the medium is air, the pressure is 101325Pa, the temperature is 20 ℃, the density is 1.2kg / m 3 , and the relative humidity is 50% status.

    Product number Rotating speed
    r / min
    Serial number Flow m 3 / h Full pressure Pa Electric motor
    Type Power kW
    4-72 № 2.8 A 2900 1 1131 ~ 2356 994 ~ 606 Y90S-2 (B35) 1.5
    4-72 № 3.2 A 2900 1 1688 ~ 3517 1300 ~ 792 Y90L-2 (B35) 2.2
    1450 1 844 ~ 1758 324 ~ 198 Y90S-4 (B35) 1.1
    4-72 № 3.6 A 2900 1 2664 ~ 5268 1578 ~ 989 Y100L-2 (B35) 3
    1450 1 1332 ~ 2634 393 ~ 247 Y90S-4 (B35) 1.1
    4-72 № 4 A 2900 1 4012 ~ 7149 2014 ~ 1320 Y132S 1 -2 (B35) 5.5
    1450 1 2006 ~ 3709 501 ~ 329 Y90S-4 (B35) 1.1
    4-72 № 4.5 A 2900 1 5712 ~ 10562 2554 ~ 1673 Y132S 2 -2 (B35) 7.5
    1450 1 2856 ~ 5281 634 ~ 416 Y90S-4 (B35) 1.1
    4-72 № 5 A 2900 1 7728 ~ 15455 3187 ~ 2019 Y160M 2 -2 (B35) 15
    1450 1 3864 ~ 7728 790 ~ 502 Y100L 1 -4 (B35) 2.2
    4-72 № 6 A 1450 1 6677 ~ 13353 1139 ~ 724 Y112M-4 (B35) 4
    960 1 4420 ~ 8841 498 ~ 317 Y100L-6 (B35) 1.5
    4-72 № 6 D 1450 1 6677 ~ 13353 1139 ~ 724 Y112M-4 4
    960 1 4420 ~ 8841 498 ~ 317 Y100L-6 1.5
    4-72 № 8 D 1450 1 15826 ~ 29344 2032 ~ 1490 Y180M-4 18.5
    960 1 10478 ~ 19428 887 ~ 651 Y132M 2 -6 5.5
    730 1 7968 ~ 14773 512 ~ 376 Y132M-8 3
    4-72 № 10 D 1450 1 40441 ~ 56605 3202 ~ 2532 Y250M-4 25
    960 1 62775 ~ 37476 1395 ~ 1104 Y200L 1 -6 18.5
    730 1 20360 ~ 28497 805 ~ 637 Y160L-8 7.5
    4-72 № 12 D 960 1 46267 ~ 64759 2013 ~ 1593 Y280S-6 45
    730 1 35182 ~ 49244 1160 ~ 919 Y225S-8 18.5
    4-72 № 6 C 2240 1 10314 ~ 20628 2734 ~ 1733 Y160L-4 15
    2000 1 9209 ~ 18418 2176 ~ 1380 Y160M-4 11
    1800 1 8288 ~ 16576 1760 ~ 1116 Y132M-4 7.5
    1600 1 7367 ~ 14734 1389 ~ 881 Y132S-4 5.5
    1250 1 5756 ~ 11511 846 ~ 537 Y100L 2 -4 3
    1120 1 5157 ~ 10314 679 ~ 431 Y100L 1 -4 2.2
    1000 1 4605 ~ 9209 541 ~ 344 Y100L 1 -4 2.2
    900 1 4144 ~ 8288 438 ~ 278 Y90L-4 1.5
    800 1 3684 ~ 7367 346 ~ 220 Y90S-4 1.1
    4-72 № 8 C 1800 1 19646 ~ 25240 3143 ~ 3032 Y200L 1 -2 30
    2 28105 ~ 36427 2920 ~ 2302 Y200L 2 -2 37
    1600 1 17463 ~ 22435 2478 ~ 2390 Y180M-2 twenty two
    2 24982 ~ 32380 2303 ~ 1816 Y200L 1 -2 30
    1250 1 13643 ~ 25297 1507 ~ 1106 Y160M-4 11
    1120 1 12224 ~ 15705 1209 ~ 1166 Y132M-4 7.5
    2 17487 ~ 22666 1124 ~ 887 Y160M-4 11
    1000 1 10914 ~ 14022 963 ~ 929 Y132S-4 5.5
    2 15614 ~ 20237 895 ~ 707 Y132M-4 7.5
    900 1 9823 ~ 12620 779 ~ 752 Y112M-4 4
    2 14052 ~ 18213 725 ~ 572 Y132S-4 5.5
    800 1 8732 ~ 16190 615 ~ 452 Y100L 2 -4 3
    710 1 7749 ~ 9956 485 ~ 468 Y100L 1 -4 2.2
    2 11085 ~ 14368 450 ~ 356 Y100L 2 -4 3
    630 1 6876 ~ 12749 381 ~ 280 Y100L 1 -4 2.2
    4-72 № 10 C 1250 1 34863 ~ 48797 2373 ~ 1877 Y225S-4 37
    1120 1 31237 ~ 43722 1902 ~ 1505 Y200L-4 30
    1000 1 27890 ~ 39038 1514 ~ 1199 Y180M-4 18.5
    900 1 25101 ~ 35134 1225 ~ 970 Y160L-4 15
    800 1 22312 ~ 31230 967 ~ 766 Y160M-4 11
    710 1 19802 ~ 27717 761 ~ 603 Y132M-4 7.5
    630 1 17571 ~ 24594 599 ~ 475 Y132S-4 5.5
    560 1 15618 ~ 21861 473 ~ 375 Y112M-4 4
    500 1 13945 ~ 19519 377 ~ 299 Y100L 2 -4 3
    4-72 № 12 C 1120 1 53978 ~ 75552 2746 ~ 2172 Y280S-4 75
    1000 1 48195 ~ 56739 2185 ~ 2070 Y225M-4 45
    2 60397 ~ 647457 1969 ~ 1729 Y250M-4 55
    900 1 43375 ~ 60712 1767 ~ 1399 Y250M-6 37
    800 1 38556 ~ 45391 1395 ~ 1321 Y200L 2 -6 twenty two
    2 48317 ~ 53966 1257 ~ 1104 Y225M-6 30
    710 1 34218 ~ 47895 1097 ~ 869 Y200L 1 -6 18.5
    630 1 30362 ~ 42498 863 ~ 684 Y180L-6 15
    560 1 26989 ~ 29381 682 ~ 673 Y160M-6 7.5
    2 31774 ~ 37776 646 ~ 540 Y160L-6 11
    500 1 24097 ~ 33728 543 ~ 430 Y160M-6 7.5
    450 1 21687 ~ 23610 440 ~ 434 Y132M 1 -6 4
    2 25532 ~ 30356 417 ~ 348 Y132M 2 -6 5.5
    400 1 19278 ~ 26983 347 ~ 275 Y132S-6 3

    4-72 № 16 B

    900 1 102810 ~ 111930 3157 ~ 3115

    Y315L 2 -6

    132

    2 121040 ~ 143910 2990 ~ 2497 Y355M 1 -6 160
    800 1 91392 ~ 127920 2489 ~ 1969 Y315L 1 -6 110
    710 1 81110 ~ 113520 1957 ~ 1549 Y315S-6 75
    630 1 71971 ~ 100730 1538 ~ 1218 Y280M-6 55
    560 1 63974 ~ 89544 1214 ~ 961 Y250M-6 37
    500 1 57120 ~ 79950 967 ~ 766 Y225M-6 30
    450 1 51408 ~ 71955 783 ~ 620 Y200L 1 -6 18.5
    400 1 45696 ~ 63960 618 ~ 490 Y180L-6 15
    355 1 40555 ~ 56764 487 ~ 386 Y160L-6 11
    315 1 35985 ~ 50368 383 ~ 303 Y160M-6 7.5
    4-72 № 20 B 710 1 158410 ~ 221730 3069 ~ 2427 JS138-8 245
    630 1 140560 ~ 196750 2411 ~ 1908 Y355M 3 -8 160
    560 1 124950 ~ 174890 1902 ~ 1505 Y315L 2 -8 110
    500 1 111560 ~ 156150 1514 ~ 1199 Y315M-8 75
    450 1 100400 ~ 140530 1225 ~ 970 Y315S-8 55
    400 1 89250 ~ 124920 967 ~ 766 Y280S-8 37
    355 1 79209 ~ 110860 761 ~ 603 Y250M-8 30
    315 1 70284 ~ 98376 599 ~ 475 Y225M-8 twenty two
    280 1 62475 ~ 87445 473 ~ 375 Y200L-8 15
    250 1 55781 ~ 78076 377 ~ 299 Y180L-8 11

    Type and structure <br /> When viewed from the side of the motor, the impeller rotating clockwise is called a clockwise rotating fan, which is expressed as "clockwise", and the impeller rotating counterclockwise is called a counterclockwise rotating fan. "Said.
    The outlet position of the fan is indicated by the outlet angle of the casing. 4-72 type fan: №2.8 air outlet position adjustment range 0 ° ~ 225 °, the interval is 45 °. №3.2 ~ 6 The position of the air outlet can be adjusted from 0 ° to 225 °, and the interval is 22.5 °. №8 ~ 12 air outlet position adjustment range is 0 ° ~ 225 °, the interval is 45 °. №16, 20 air outlet positions are made of three fixed types: 0 °, 90 °, 180 °, which cannot be adjusted. Please specify when ordering.
    In type 4-72, №2.8 ~ 6 uses A-type transmission, №8 ~ 12 uses C and D type transmission, and №16 ~ 20 uses B type transmission.
    №2.8 ~ 6 of 4-72 type fan are mainly composed of direct-connected motors such as impeller, casing and air inlet. №8 ~ 20 include transmission parts in addition to the above.
    Fourth, the installation and use of the fan < br 安装 Before installation, first prepare the installation materials and tools, and check the parts of the fan. The impeller, the main shaft and the bearings should be inspected particularly carefully. If damage is found, it should be repaired, and then the inside of the bearing box should be cleaned with kerosene.
    The following points must be noted during the installation operation:
    1. On some joints, in order to prevent rust and reduce the difficulty of disassembly, some grease and mechanical oil should be applied.
    2. When attaching the bolts on the joint surface, if there is a positioning pin, the pin should be installed before tightening the bolt.
    3. Check that there are no tools or debris falling into the cabinet and other housings.
    Installation requirements:
    1. When installing the fan, the weight of the gas pipeline should not be added to the casing. Pay attention to the gap between the air inlet and the impeller, and keep the shaft horizontal.
    2. When installing the air inlet duct, you can directly use the bolt connection of the air inlet itself. At this time, the air inlet is fixed by three countersunk screws.
    3. When the air outlet is installed at an angle, the rear cover is properly rotated to keep the label in a horizontal position.
    4. When installing №8 ~ 12D fan, use a dial indicator and feeler gauge to measure the coaxiality of the fan main shaft and the motor shaft and the non-parallelism of the two ends of the coupling. The tolerance of the non-parallelism of the two axes is 0.05mm. The tolerance of the non-parallelism of the coupling end face is 0.1mm.
    5. After the fan is installed, move the rotor by hand or lever to check whether there is overtightness or collision. Only test the rotation without these phenomena.
    6. After the motor is installed, install pulleys, couplings, and guards. If the air inlet is not connected to the air inlet duct, add protective nets or other safety devices (user-supplied).
    The power of the motor used by the fan refers to the power required under the specific working conditions, plus the mechanical loss and the reserve that should be in place, when the air outlet is fully open. If the outlet or inlet of the fan is run dry without being connected to the pipeline or without external resistance, the motor may be burned. For safety reasons, a valve should be added to the fan's outlet or inlet pipeline, and it should be closed when the motor is started, and the valve should be slowly opened after running until the specified operating conditions are reached, and pay attention to whether the motor current exceeds the specified value.
    V. Fan maintenance ㈠ Fan maintenance work system Fan maintenance personnel must pay attention to the following points:
    1. Operate only when the fan equipment is completely normal.
    2. If the fan adjusting equipment starts after maintenance, please pay attention to whether the parts of the fan are normal.
    3. Regularly remove dust, dirt, water and other impurities inside the fan and gas transmission pipeline, and prevent rust.
    4. The cleaning of fan equipment must not be carried out during operation.
    注意 Precautions during normal fan operation
    1. If it is found that the flow is too large, does not meet the requirements for use, or a small flow is required in a short period of time, it can be adjusted with a throttle device.
    2. Regularly check the sensitivity of the thermometer and oil gauge.
    3. When the fan is running, stopping or running, if abnormality is found, it should be checked immediately.
    4. For minor faults found during inspection, the cause should be promptly identified, and measures should be taken to eliminate or deal with them. If minor faults cannot be eliminated, or major faults are found, they should be repaired immediately.
    5. In addition to replacing the lubricant after each disassembly, the lubricant should also be changed regularly.
    主要 The main faults and causes of the fans are:
    1. The bearing box vibrates violently. ① The fan shaft is not concentric with the motor shaft, and the coupling is incorrectly installed.
    ② The casing or air inlet rubs against the impeller.
    ③ The stiffness of the foundation is insufficient or not strong.
    ④ The impeller rivets are loose or the disk is deformed.
    ⑤ The impeller shaft disc and shaft are loose, and the coupling bolts move.
    ⑥ The connecting bolts such as casing and bracket, bearing box and bracket, bearing box cover and seat are loose.
    不良 The air inlet and outlet pipes of the fan are badly installed.
    不 The rotor is unbalanced.
    ⑨ The pipe network is too thin and the wind speed is too fast.
    2. The temperature of the bearing is too high ① The bearing box vibrates violently.
    ② The quality of bearing lubricating grease is bad, deteriorated, and contains impurities such as dust, sticky sand and dirt.
    ③ The tightening force of the bearing box cover and seat connection bolt is too large or too small.
    ④ The shaft and rolling bearing are installed at an angle, and the front and rear bearings are not aligned.
    ⑤ The rolling bearing is damaged.
    3. The motor current is too high and the temperature rise is too high ① The gate or throttle in the intake pipe is not closed tightly when driving.
    ② The flow exceeds the specified value or the air pipe is leaking.
    ③ The density of air conveyed by the fan is too large, which makes the pressure too large.
    ④ The motor input voltage is too low or the single-phase power supply is powered off.
    ⑤ The coupling is not properly connected, the aprons are too tight or the gaps are uneven.
    ⑥ Affected by the severe vibration of the bearing box.
    Six, ordering instructions <br /> When ordering, the machine number, speed, air volume, pressure, air outlet angle and rotation direction of the fan must be indicated, and the motor model specifications.

    Seven, appearance and installation dimensions



  • Installation and dimensions of 4-72 and B4-72 №2.8A ~ 6A centrifugal fans     (Note: The motors for B4-72 are YB)

      • Machine number Into the wind pass Out of the wind
        D 1 D 2 D 3 Connecting bolt B 1 B 2 B 3 B 4 B 5 B 6 Bolt hole
        specification Number diameter Number spacing
        ×L 1 M (d 1 ) × L 1 n 1 d 2 n 2 n 3 × b 1 n4 × b2
        8 №2 . 8 Equipped with motor
        B35
        type
        YB90S-2 Y / YB90S-2 φ 280 φ 306 φ 324 M8 × 10 8 196 228 251 224 256 278 φ 7 16 4 × 57 4 × 64
        2 №3 . 2 YB90S-4 Y / YB90S-4 φ 320 φ 350 φ 367 M6 × 10 16 224 256 279 256 288 310 φ 7 16 4 × 64 4 × 72
        YB90L-2 Y / YB90L-2
        6 №3 . 6 YB90S-4 Y / YB90S-4 φ 360 φ 394 φ 416 M6 × 16 16 252 284 308 288 320 343 φ 7 16 4 × 71 4 × 80
        YB100L-2 Y / YB100L-2
        №4 YB90S-4 Y / YB90S-4 φ 400 φ 440 φ 462 M6 × 16 16 280 315 336 320 355 375 φ 7 20 5 × 63 5 × 71
        YB132S 1 -2 Y / YB132S 1 -2
        5 №4 . 5 YB90S-4 Y / YB90S-4 φ 450 φ 490 φ 512 M8 × 20 16 315 350 371 360 395 415 φ 7 20 5 × 70 5 × 79
        YB132S 2 -2 Y / YB132S 2 -2
        №5 YB100L 1 -4 Y / YB100L 1 -4 φ 500 φ 550 φ 572 M8 × 20 16 350 385 406 400 435 456 φ 7 20 5 × 77 5 × 87
        YB160M 2 -2 Y / YB160M 2 -2
        №6 YB100L-6 Y / YB100L-6 φ 600 φ 650 φ 676 M8 × 20 16 420 456 476 480 510 536 φ 7 twenty four 6 × 76 6 × 85
        YB112M-4 Y / YB112M-4
        Machine number Security equipment and external dimensions Y motor
        A 1 A 2 A 3 A 4 A 5 B 7 B 8 E 1 E 2 E 3 E 4 E 5 E 6 H 1 H 2 Anchor bolt L Motor weight kg
        ×L 2 M (d 3 ) × L 2
        8 №2 . 8 196 5 100. 5 210 100 140 180 150 459 187 272 226 310 565 90 185 M8 × 220 485 twenty one
        2 №3 . 2 224 5 114. 5 224 100 140 180 150 523 213 310 258 354 641 90 185 M8 × 220 514 twenty two
        5 236. 5 125 140 180 170 90 539 twenty four
        6 №3 . 6 252 129 239 100 140 180 150 588 5 239. 5 5 348. 5 5 290. 5 5 398. 5 718 90 185 M8 × 220 543 twenty two
        266 140 160 205 185 100 M10 × 220 603 32
        №4 280 143 253 100 140 180 150 652 5 265. 5 5 38.6 . 5 322 5 442. 5 794 90 185 M8 × 220 571 twenty two
        306 140 216 280 210 132 M10 × 220 706 65
        5 №4 . 5 315 5 160. 5 5 270. 5 100 140 180 150 732 298 434 5 362. 5 5 497. 5 889 90 185 M8 × 220 606 twenty two
        5 323. 5 140 216 280 210 132 M10 × 220 741 70
        №5 350 178 311 140 160 205 185 814 331 483 403 553 985 100 185 M8 × 220 701 32
        391 210 254 330 275 160 260 M10 × 220 871 123
        №6 420 231 5 351. 5 140 160 205 185 974 396 578 483 663 1176 100 185 M8 × 220 771 30
        5 358. 5 140 190 245 195 112 M10 × 220 791 45

        4-72, B4-72 № 8, 10, 12 C (D) Centrifugal Fan Installation and Dimensions
        Machine number Into the wind Out of the wind
        D 1
        D 2
        D 3
        Connecting bolt
        B 1
        B 2
        B 3
        B 4
        B 5
        B 6
        Connection bolt hole
        specification
        Number
        diameter
        Number
        Interval
        M (d 1 × L)
        n 1
        d 2
        n 2
        n 3 × b 1
        n 4 × b 2
        № 8
        φ 800
        φ 860 φ 910 M10 × 20 16 560 624 669 640 700 746 φ 15 26 6 × 104 7 × 100
        № 10
        φ 1000  
        φ 1065 φ 1100 M12 × 20 16 700 765 809 800 860 906 φ 15 20 5 × 153 5 × 172
        № 12
        φ 1200
        φ 1270 φ 1330 M12 × 20 twenty four 840 900 949 960 1008 1066 φ 15 twenty four 6 × 150 6 × 168
        Machine number Security equipment and external dimensions




    • Yunnan Jingge Ventilation Equipment Co., Ltd.
    • Dabanqiao Industrial Park, Guandu District, Kunming City, Yunnan Province
    • 714328283@qq.com
    • hotline:
    • 13759168650
    • Jing grid fan-believe in the power of the brand
    Copyright © Yunnan Jingge Ventilation Equipment Co., Ltd. All Rights Reserved. Dian ICP No.16007375-1 Website Construction Technical Support: Yunnan Dinghao Information Technology Co., Ltd
    七乐彩 欢乐拼三张 欢乐拼三张 天天电玩城